• Delivery RЕТОМ-61in stock
  • Warranty 5 years
  • Price on-demand

Higher current – wider test range!

RETOM-61 — based universal test set is an up-to-date solution for complicated diagnostic tasks. The set allows manual and automatic testing and debugging of all types of relay protection, from electromechanical panel to microprocessor terminals.

Flexibility in application:

  • internal microcomputer provides RETOM-61 operation with any Windows 2000/XP/Vista/Seven/8-operated PC;
  • Instrument/PC Ethernet link enhances communication speed and allows to control several RETOM-61 by one PC. Combination of 10 instruments in one set allows to carry out dynamic test and transients modeling using up to 60 current and 40 voltage channels;
  • two three-phase current systems permit easy and rapid test of transformer differential protection;
  • three-phase output current increased to 72 А, meanwhile power per channel is 1000 VA;
  • 200 A single-phase maximum output current allows to cover up to 90% of current settings used;
  • four voltage supply units allows to configure three-phase voltage system and 3U0 galvanically separated channel;
  • up to 405 V single-phase voltage permits to test 0,4 kV relay circuits;
  • frequency range increased to 1000 Hz;
  • a special DC voltage supply unit (=U) is provided to energize the device under test;
  • the device is equipped with full-function dual channel oscilloscope-multimeter;
  • internal high-resolution (0.1 ms) 16-input discrete analyzer allows to analyze response of the protection under test to the maximum;
  • 8 output relays allow to set any binary signal combinations for complicated protection systems test, IED in particular;
  • PC connection is made thru Ethernet port.

Serviceability:

  • three-phase voltage system together with 3U0 channel permit to test complicated protections that need y-connection and open delta connection (or capacitive voltage transformer cubicle connection), auto-synchronizers etc.;
  • RЕТOM-61850 switching module permits to test IED protections according to IEC 61850 standard requirements;
  • RЕТ-64/32 module usage allows to increase number of binary inputs up to 80 and outputs up to 40;
  • using RЕТ-GPS modules it is possible to synchronize operation of two systems widely spaced apart which is a unique possibility to test simultaneously both OL protection subsystems located at its ends;
  • single-phase current transformer RЕТ-10 is designed for current scaling with 10, 6 and 0.1 ratios which permits to obtain valid current measurement from 1mA to 720A channel;
  • three-phase voltage transformer RЕТ-ТN is intended to scale voltage with 1/v3; 1; v3 and 5 ratios which allows to test relay protection and automation system for 0.4 and 0.66 kV, energy meter including;
  • all connectors are located on the front panel permitting to operate the device both in vertical and in horizontal position;
  • RЕТОМ-61internal microcomputer provides operation with any Windows XP/Vista/Seven/8-operated PC;
  • friendly and Windows-conventional interface;
  • free software suit permits in manual and semi-automatic mode and a special suit in automatic mode to test easily and rapidly any relay and protection.;
  • RЕТОМ-61 open control architecture allows user to create his own test programs with wide range of automation;
  • use of standard Windows facilities for preparation of protocols permits to facilitate report creation;
  • single PC-based parallel operation of several RЕТОМ-61 devices permits to obtain necessary number of current and voltage sources;
  • convenient way of software updating allows to use the latest version;
  • joint operation with RЕТОМ-VCH enables user to carry out full-scale test of instantaneous carrier-pilot phase comparison protection subsystem.

Safety and reliability:

  • IED with a wide-range internal monitoring provides high safety both for the device itself and for equipment under test;
  • in case of emergency all output signals are switched off and test process is stopped until recovery. This essentially increases security of test works and verification of the data;
  • analog input isolation provides secure measurement of external voltages;
  • channel accident-free terminals provide protection against electric shock;
  • safety operation within a wide range of line voltage;
  • robust and aesthetically pleasing device case is resistant to mechanical impacts.

Application

RЕТОМ-61 system provides possibility to test and setup relay protections of all generations both in manual and in automatic modes:

  • state-of-art home and foreign microprocessor relay and sophisticated protection systems;
  • semi-conductor relay protection and automation devices;
  • the whole range of electric panels, protection and automation sets;
  • home and foreign fault detectors;
  • out-of-step protection panels and remote measurement circuits;
  • sync devices;
  • energy counters;
  • generator excitation systems;
  • railway protections.

Delivery set

PC-controlled RЕТОМ-61 system delivery set includes:

  • RЕТОМ-61 test instrument;
  • standard software consisting of the following modules::
    • Manual control for current and voltage sources
    • Current relay test
    • Voltage relay test
    • Directional power relay test
    • Resistance relay test
    • Frequency relay test
    • Universal stopwatch register
    • Digital oscilloscope record fault display
    • Power system model
    • RETOM-Master special test program development language
    • Test data generator

Transformer differential protection

  • accessories;
  • supporting documents.

Optional delivery:

  • special programs for automatic test of different relay and packaged protection systems ;
  • RЕТ-TN three-phase voltage transducer unit;
  • RЕТ-10 single-phase current transducer unit;
  • RЕТ-GPS sync unit;
  • RЕТ-64/32 input/output expansion unit;
  • Notebook;
  • printer;
  • РЕТОМ-61 robust transporting case.
CURRENT SOURCES

Q-ty, pcs

6 independent sources

Current measuring range, A

- 1-phase

- 3-phase

- 6-phase

- DC range

 

200 A (700 VA)

72 A

36 A (1400 VA)

30 A

Min. current regulation step, mA

1,0

Max. output voltage (peak-to-peak), V, min

34

DC and AC current value permissible absolute error limits (RMS value), A**

±(0.004x + 0.00004Xk)

Overvoltage protection operation level, V (RMS)

24

VOLTAGE SOURCES

Q-ty, pcs

4 independent sources, including one ground-isolated source

Voltage measuring range, V

- 4-phase

135 (135 VA)

- DC range (shunt connection of sources)

380 (80 W)

Min. voltage regulation step, mV

10

Max. output power / source (Uout Ω 60 V), VA, min

80

AC and DC voltage value permissible absolute error limits, V**

±(0.004x + 0.00004Xk)

Short-circuit protection operation level, A

- @ output voltage RMS value below 60 V

- @ output voltage RMS value over 60 V

 

1.0

0.6

DC voltage ripple ratio at load resistance 4.3k Ω, % of measured value, max.

0.1

AUXILIARY DC VOLTAGE SOURCE

Output voltage range, V

130 - 264

Output current, A

1.25

Max. output power, W

300

Peak-to-peak ripple in 0 - 20 MHz frequency range at 220V output voltage and max. output power, %, max

± 1

CURRENT AND VOLTAGE SOURCES

Reproducible frequency range for current source, Hz

1 - 1000

Reproducible frequency range for voltage source, Hz

1 - 2100

Min. frequency increment step, Hz

0.001

Frequency accuracy permissible absolute error limits, Hz**

- frequency range at 45...65 Hz

 

±0.0002

- frequency range below 45 and over 65 Hz

±0.01

Phase shift angle variation @ fundamental frequency, °

0 - 359.999

Phase shift angle setting permissible absolute error limits (5 to 100% signal amplitude reproduction range), ° **

± 0.3

ANALOG INPUTS

Nr. of inputs, pcs

2 (isolated)

Voltage measurement limits, V

0.5-5 5-50

Voltage measurement permissible absolute error limits, V **

±(0.005X + 0,0001Xk)

Measured voltage min. permissible value, % of the limit

130

Integrated voltmeter input resistance, k Ω, min.

1000
BINARY INPUTS

Nr. of inputs, pcs

16 (isolated)

Type

"dry contact", transistor switch, TTL 15 V

Max. DC input voltage, V

300

Input state reading uncertainty time, ms

0.1

Input status change detection resolution, ms, max

0.2

BINARY OUTPUTS

Nr. of inputs, pcs

4

4
Type Transistor Relay  

Making capacity at resistive load:

- DC current value, A

- DC voltage value, V

 

0.12 

400

 

5         

250

Making capacity at resistive load:

- AC current value, A

- AC voltage value, V

 

0.085

285

 

16

250

Operate/reset time, ms

2 20
MILLISECOND TIMER

Time measurement range, c

0.001 - 99 999

Time interval presentation permissible relative error limits, % **

± 0.1

Time interval presentation permissible absolute error limits, ms **

± (0.001x+0.3)

GENERAL DATA

Power circuit insulation to case test voltage ***, V

1500

Conductive parts (except analog inputs) insulation to case/supply circuits test voltage ***, V

1500

Analog inputs insulation to case/supply circuits test voltage ***, V

2200

Binary inputs insulation (relative to each other) test voltage, V

500

Test set power supply:

- single-phase network

- supply circuit frequency, Hz

- power consumption, VA, max

 

220 - 22 (+ 44)

48-51

3600

Test set weight, kg, max

20.5

Overall dimensions (w/o test switch), mm, max.

510 х 180 х 485

GENERAL DATA

Ambient operating temperature range, °С

5 - 40

Relative humidity @ 25 ΩC, %, max. °С, %, не более

80

Altitude, m, max.

2000

Storage temperature range, °С

-50 ... +50

Service conditions group per GOST 17516.1-90

М23

Protection level per GOST 14254-96

IP20

Safety specification per GOST 51350-99

Class I

RELIABILITY PERFORMANCE

Mean lifetime, years, min.

30

MTBF (Mean time between failures), hr, min

10000

Reclaim mean time, considering troubleshooting time, hr, max.

3

 

Note:
The following designations are used in relative error equations:
Хк- measuring limit of respective value;
X
- measured magnitude of respective value;
R
н - load resistance (real)
Rном - load resistance at rated power

to top