• Delivery RЕТОМ-21in stock
  • Warranty 5 years
  • Price on-demand

Only high-quality test of electrical equipment!

In 2016 RETOM-21 was modified in a number of ways:

  • the weight of the test device was reduced for 7 kg;
  • the accuracy of the output data settings was increased by 10 times;
  • the maintenance of the equipment became even easier thanks to the new layout of controls: all the elements and programming module indicators are accessible in a single window;
  • the Source 3 can be controlled via PC;
  • programming module “Current Transformer” employs a wider range of the excitation curve in automatic mode(up to 2000 V), which allows users to promptly check CT with the knee point of an excitation curve up to 1800 V;
  • additionally, demagnetization of transformers is made automatic, which provides an adequate functioning of the protective relay;
  • software design and interface were updated, making the latter more friendly and intuitive. The software can be used by specialists with no prior experience and qualifications.

All these modifications allowed to improve the usability of the equipment.

RETOM-21 is a basic device of the testing system intended for testing of primary and secondary electrical equipment. Technical data:

  • max. output current of up to 800 A;
  • max. output voltage of up to 500 V;
  • sustainable maximum power up to 2500 and 4500 VA respectively;
  • adjustment of current, voltage, frequency, phase (angle);
  • multimeter allows to measure current, voltage, frequency and phase;
  • auxiliary DC power source;
  • full-featured CT maintenance check etc.

RETOM-21 is a certified measuring equipment.

Delivery kit

  • RETOM-21;
  • network cable;
  • operational manual;
  • user manual;
  • spare tools and accessories kit.

Warranties

SPE Dynamics assures the quality and reliability by providing a 5-year warranty on the testing equipment

Source 1. OUTPUT "=U1". Adjustable DC voltage

Parameter

Value

Voltage adjustment range, V

176-264

Rated output power, W, at least:

220

Voltage ripple range at Uout=220 V and rated output power, %, max.

1

Output activation time delay, s, max.

2

Output circuit fault and overload protection

+

Source 2. OUTPUT "~U2". Adjustable AC voltage

Parameter

Value

Operation range, to be selected in the menu

10

65

250

Output voltage adjustment range, V

0-10

0-65

0-250

Ouput current adjustment range, A

0-10

0-1.5

0-0.6

Output signal change sampling rate, %, max.

0.2

Output power, VA, at least:

 

            - rated

100

            - during 5 s

150

Non-linear distortion ratio, %, max.

1.0

Reproduced frequency range, Hz

20-45

more than 45-55

more than 55-1000

Frequency change sampling rate, Hz, max.

0.5

0.001

0.5

Range of permissible absolute frequency change error, Hz

+0.5

+0.001

+0.5

Phase change range, degrees

0-360

Phase change sampling rate, degrees, max.

0.3

Range of permissible absolute phase change error, degrees

+1

Output circuit fault and overload protection

+

Output circuit voltage protection, V RMS, <1000 VA

12

75

264

Source 3. OUTPUTS "~U3", "=U4", "~U5", "~U6"

Parameter

Value

Power supply single phase mains frequency, Hz

45-65

Source 3. OUTPUT "~U3". Adjustable AC current or voltage

Parameter

Value

Switch position

500 V

250 V

50 A

Current adjustment range, A

0-8

0-16

0-100

Voltage adjustment range, V

11.5-500

6-250

0.95-40

Output power, VA, at least:

 

            - rated

2000

            - during 1 min

2500

            - during 5 s

3600

Source 3. OUTPUT "#ИМЯ?;. Adjustable DC or rectified (unsmoothed) voltage

Parameter

Value

Switch position

Выход U4

Menu item for Source 3 DC

"Выпрямленн." (Rectified)

"Сглаженный" (Smoothed)

Current

Rectified

DC

Voltage adjustment range, V

8-250

10-350

Current adjustment range, A

0-10

0-5

Max. switching current, output "#ИМЯ?;

8

1

Rated output power, W

2000

150

Source 3. OUTPUT "~U5". Adjustable AC current

Parameter

Value

Switch position

200 A

Current adjustment range, A

0-700

Voltage adjustment range, V

0-9

Output power, VA, at least:

 

            - rated

1800

            - during 1 minute

2400

            - during 1 s

4500

Source 3. OUTPUT "~U6. Adjustable AC voltage

Parameter

Value

Output voltage adjustment range, V

5-240

Rated output current, A

 

            - rated

10

            - during 5 s

20

            - during 0,5 s

30

Output power, VA, at least:

 

            - rated

2000

            - during 1 minute

2500

            - during 5 s

4500

            - during 0,5 s

6000

Source 3. Ballast resistor

Parameter

Value

Resistance, Ohm

0

282

Rated output current, A

rated

during 1 minute

BUILT-IN DIGITAL MULTIMETER

Parameter

Value

Current

DC/AC

Ammeter

Ammeter resolution, A

0.0001

0.001

0.01

0.1

"Source 1" (I1) DC measuring limits, A

-

2.0

-

-

"PA" input measuring limits, A

0.1

1.0

10

-

"Source 2" (I2) measuring limits, A

0.2

2.0

20

-

"Source 3" (I3) measuring limits, A

0.5

5.0

50

-

"Source 3" (I4) measuring limits, A

0.5

5.0

50

-

"Source 3" (I5) measuring limits, A

-

-

70

700

Min.permissible measured  value, % of measuring limit

10

Range of permissible absolute basic current measuring error:

 

                        - for "70 A, 700 A" limits

+ [0.01x+0.001Xk]

                        - for other limits, except 2 A (I1), 70 A, 700 A

+ [0.005x+0.0005Xk]

Current measuring time, minimum, ms

1

Voltmeter
Voltage measuring limits, V

6

600

Voltmeter resolution, V

0.001

0.1

Voltage measuring time, minimum, ms

1

Min.permissible measured  value, % of measuring limit

1

Voltage inputs overload capability, % of measuring limit

130

Range of permissible absolute basic voltage measuring error:

+ [0.005x+0.0005Xk]

Voltmeter input resistance, kOhm, not less

1000

Frequency counter
Frequency measuring ranges on votage inputs, Hz

20-45

45-55

55-1000

Frequency counter resolution, Hz

0,01

0,001

0,1

Range of permissible absolute basic frequency measuring error

+ 0.05

+ 0.005

+ 0.05

Min.permissible voltage level when measuring frequency, mB

600

Phase meter

Phase angle measuring range, degree

0-360

Phase measuring resolution, degree

0.1

Range of permissible absolute basic angle measuring error, degree

+1,0

Min.permissible voltage level when measuring angle, mB

600

Additionally calculated parameters

P; Q; S; Z; R; XL; XC; TG; COS

BUILT-IN DIGITAL TIMER

Parameter

Value

Measuring limits

0-999.9 ms

1.000-9.99 s

10.00-99.99 s

100.0-999.9 s

1000-9999 s

Resolution

0.1 ms

0.001 s

0.01 s

0.1 s

1 s

Range of permissible absolute time measuring error

+0.5 ms

+0.01 s

+0.1 s

+1 s

Time parameter measuring:

 

            - operating time

+

            - reset time

+

            - close (open) state duration

+

            - time difference between contact  operation and release

+

            - bounce duration

+

Binary input:

 

            - binary input type

"dry contact"; potential max.+300 V

Binary output:

 

            - binary output type

Contact with load capability up to ~5 A, 250 V and =5 A, 30 V

            - binary output circuit protection – thermodisconnector:

            - rated current, A

4,5

OPTIONAL FUNCTIONS

Parameter

Value

Source 3 single-pulse operating mode

 

            - pulse generation time change range

20-100 ms, 20 ms step

100-1000 ms, 100 ms step

1-10 s, 1 s step

            - factory setting, ms

100

Source 3 pulse operating mode

 

            - pulse generation time and dead-time change range

20-100 ms, 20 ms step

100-1000 ms, 100 ms step

1-5 s, 1 s step

            - factory setting, ms

500

Measurement in pulse modes

 

            - whole range 20 ms – 10 s

any manually set measuring limit

            - for 20-300 ms

Input PV1, PV2 limit "2.5 V";
output I5 limit "300 A"; input PA limit "10A"

            - for 400 ms – 10 s

All limits of outputs U3-U6, I3, I5; inputs PV1, PV2, PA

Current capture (from PV1, PV2, PA, I2, I3, I5 meters)

 

            - count stop signal for PV1 and PV2 inputs (default limit "2,5 V")

Voltage decrease to 0.1 of limit (0.25 V for limit "2.5V")

            - count stop signal for PA input and I2, I3, I5 outputs

Current decrease to 0.1 of limit (1 A for limit "10 A")

            - measurement sampling rate, ms

2.5

Timer contact vibration offset filter:

 

            - time constant change range, ms

1-40

            - factory setting, ms

3

Bounce time measurement:

 

            - range of contact close latch delay change, ms

0.1-10.0

            - factory time delay setting, ms

1.0

Note – Pulse mode time intervals at 50 Hz

OPERATING CONDITIONS

Parameter

Value

Operating temperature range, ºC

-20…+50

Normal temperature, ºC

20+5

Storage temperature range, ºC

-50…+50

Relative humidity at 25 ºC, %, max.

80

Altitude, m, max.

2000

Operating conditions group acc.to GOST 17516.1-90

M23

Power supply:

 

            - single phase mains frequency, Hz

45-65

            - mains voltage, V

187 – 264

GENERAL TECHNICAL DATA

Parameter

Value

Protection degree acc. to GOST 14254-96:

 

            - enclosure

IP20

            - output terminals

IP00

Safety requirements acc. to GOST R 51350-99:

Class I

            - insulation

Basic

            - mounting type (overvoltage level)

CAT II

            - environmental pollution level

2

Test voltage for insulation resistance check*, V:

            - mains supply circuits against case

            - Source 1, Source 2 conducting parts against mains supply circuits/case

            - Source 3 conducting parts against mains supply ircuits/case

 

1500

 

1500

 

1500

            - Timer input "K1", "K2" against mains supply circuits/case and against each other

 

1500

            - between conducting parts (against each other)

1500

Insulation resistance between the case and galvanically insulated conducting parts, Mohm, at least

40

EMS class (acc. to GOST R 51522-99)

Class A

Rated power consumption, VA, max.

3000

Max. current consumption, A

30

Weight, kg, max.

28

Overall dimensions, mm, max.

540 x 460 x 300

*AC voltage, 50 Hz

RELIABILITY

Parameter

Value

Mean service life time, years, at least

30

MTBF, hours, at least

10000

Mean time of recovery, troubleshooting time incl., hours, max.

3

 

to top